Order NowProduct Details:
Product Code:
SensoMAG S30
Description:
Operating Voltage Range . . . . . . . . . . . . . . . . . . 9 - 30 V DC (Nom. 12/24VDC)
Average current consumption in quiescent state . . < 50µA
Alarm state current:
- with base type B24 and B24D . . . . . . . . . . . . . 20 mA / 12ё30V
- with base type B24RD . . . . . . . . . . . . . . . . . . . 33 mA / 12V; 49mA/24V; 57mA/30V
- with base type B12L/U . . . . . . . . . . . . . . . . . . 18 mA / 9V; 29mA/12V; 32mA/15V
Output in alarm state at terminal RI . . . . . . . . . . 20mA (max)/ -3.3V
(Towards terminals +IN /+OUT)
Degree of protection . . . . . . . . . . . . . . . . . . . . . IP30
Wire Gauge for terminals . . . . . . . . . . . . . . . . . . 0.4mm2 ё 2.0mm2
Operational temperature range . . . . . . . . . . . . . . -10°C ё +60°C
Relative humidity resistance . . . . . . . . . . . . . . . . (93 ± 3)% @ 40°C
Dimensions (incl. base) . . . . . . . . . . . . . . . . . . . ø102mm, h 42mm
Weight (incl. base) . . . . . . . . . . . . . . . . . . . . . . 160g